Line Type Heat Detection System Includes :
1. Analogue Linear Heat Sensing Cable
2. Digital Linear Heat Sensing Cable
Monitor and Control Unit
Fixed Temperature
68~140C
2 Levels (Pre-Alarm, Alarm)
Chose any temperature in between
Rate-of-Rise - 8~30 deg C/min
Location - Show on MCU in Meters
Fault - OC/SC Monitored
Self Adaptive - Environmental and length wise
Only Analogue Locating, Re-usable, 2 Level Fixed Temperature, Rate-of-Rise LHD in the World
Cables
Re-usable Re-settable
Analogue
Versus Digital - replace cable after Alarm
Four Core Cable
Two for temperature sensing
Thermal sensitive material
Resistance change
Two for location
3 types
High Temperature PVC - Normal
PTFE (Teflon) - Corrosion Resistant
Bronze Braid - Explosion Proof
Maximum distance per MCU
200meters - Specified by UL
Applications
Cable tunnels, Ducts & Mezzanines, Large Cable Room
Road & Rail Tunnel
Petro-Chem Storage Tank rim Seals
Conveyors - coal, Wood, etc.
Electric Room, Underground Electric Space
High Rise, Warehouse Transformer and Reactor
Outdoor or Indoor Transformer and Reactor
Nuclear Reactor Plant Area
Escalators & Moving Walkways
Vechicle Engine Compartments
Paint Shop & Spray Booths
Ceiling Voids & Attic Spaces
Marine Engine Rooms
Electrical Switchgear Cabinets
Oil Rigs & Off shore Platforms
Steam pipe Leaks & Trace Heating Faults
Computer Room Under Floor Voids
Aircraft Hanger
AlarmEye - First and only UL Listed Video Image Fire Detection System
- The New Generation and Innovative
- Distributed Intelligent Video Image
- Smoke and Flame Detection System
- First and Only UL listed
Benefits
- Distributed Intelligent System Architecture, no quantity limitation
- Early Detection
- Suitable for all-weather, all-light Environment
- Self-Learning System, Strong Immunity to False Alarm
- Obstructed Fire Detection
- Stratified Smoke Early Detection
- Locate Position or Zone of Fire
- Well Compatibility
- Easy to Use and Lower Cost